设备反控-TCP/IP反控协议

上位机与WEB平台系统TCP/IP反控协议说明

传输地址

IP1:111.85.152.192		端口: 2800 
IP2: 202.105.247.8 端口: 2800

反控示例

修改MN:[MN=GrPM1000010040](待升级)
设备校准:[W=1,F=1,K=1,B=1](待升级)

设备手动复位:{"operate":0,"device":1,"code":"01","etime":1544089350}
设备启动测量:{"operate":1,"device":1,"code":"01","etime":1544089350}
设备零点标定:{"operate":2,"device":1,"code":"01","etime":1544089350}
设备量程标定:{"operate":3,"device":1,"code":"01","etime":1544089350}
设备标样核查:{"operate":4,"device":1,"code":"01","etime":1544089350}
设备加标回收:{"operate":5,"device":1,"code":"01","etime":1544089350}

设置标液浓度:{"operate":6,"device":1,"code":"01","value":0.001}
下发因子参考数据:[{"operate":7,"device":1,"code":"01","value":0.001},{"operate":7,"device":2,"code":"02","value":0.002},{"operate":7,"device":3,"code":"03","value":0.003}]
设置设备时间:{"operate":10,"device":1,"code":"01","ctime":1544089350}

返回结果:{"result":1,"errcode":1,"errmsg"="error"}

指令内容说明

修改MN:修改设备新的MN编号为GrPM1000010040.
设备校准:校准第一个通道监测因子相关传感器.

operate:操作代码,其中包括(1:启动测量,2:零点标定,3:量程标定,4:标样核查,5:加标回收)。
device:系统设备编码,从1开始。
code:GB212编码,(上位机软件自行通过DCODE和DEV编号区分相应的串口相应的设备)。
etime:执行时间,(Unix时间戳格式,其中0表示:上位机软件收到指令后立即执行)。
value:标液浓度值,
ctime:当前时间,(Unix时间戳格式,其中0表示:上位机软件收到指令后自行通过GPS模块或者以太网获取时间。)
result:执行结果,其中0:失败,1:成功,errcode:错误代码,errmsg:错误信息。

上位机与监测设备(分析仪)反控协议说明

传输地址

串口:9600,8,N,1   (MODBUS-RTU协议)

反控示例

设备手动复位:寄存器:40058 写:0x6
设备启动测量:寄存器:40058 写:0x1
设备零点标定:寄存器:40058 写:0x3
设备量程标定:寄存器:40058 写:0x2
设备标样核查:寄存器:40058 写:0x4
设备加标回收:寄存器:40058 写:0x5

设置标液浓度:寄存器:40015-40016 写:(单精度Float,高低位交换)
设置设备时间:

指令内容说明